Measured Data

Specific Heat

Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.

Unconditioned

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1032.0 27.0
20.0 1062.0 25.0
30.0 1089.0 29.0
40.0 1099.0 27.0

Dried

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 794.0 9.0
20.0 818.0 18.0
30.0 834.0 8.0
40.0 852.0 18.0

Thermal Conductivity

Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.

Unconditioned

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.152 0.006
45.0 0.153 0.005

Dried

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.087 0.004
45.0 0.090 0.004

Mass Loss Rate (MLR)

Mass loss rate [g/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

At the 25 kW/m2 exposure the sample did not ignite.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

At the 25 kW/m2 exposure the sample did not ignite.

Cone Calorimeter: 25 kW/m2

25 kW/m² R1 25 kW/m² R2 25 kW/m² R3
Time to Sustained Ignition (s) 0.00 0.00 0.00
Time to Peak HRRPUA (s) 290.50 245.25 227.00
Peak HRRPUA (kW/m²) 21.85 28.39 19.54

Cone Calorimeter: 50 kW/m2

50 kW/m² R1 50 kW/m² R2 50 kW/m² R3
Time to Sustained Ignition (s) 44.75 45.50 33.00
Time to Peak HRRPUA (s) 7.00 5.50 7.50
Peak HRRPUA (kW/m²) 173.54 170.68 178.45

Cone Calorimeter: 75 kW/m2

75 kW/m² R1 75 kW/m² R2 75 kW/m² R3
Time to Sustained Ignition (s) 18.50 17.00 3.75
Time to Peak HRRPUA (s) 8.50 8.25 24.25
Peak HRRPUA (kW/m²) 180.43 190.00 175.09

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

At the 25 kW/m2 exposure the sample did not ignite.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.028 0.005
50 0.011 0.001
75 0.007 0.002