Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Cone Calorimeter: 25 kW/m2
|
25 kW/m² R1 |
25 kW/m² R2 |
25 kW/m² R3 |
| Time to Sustained Ignition (s) |
313.75 |
100.25 |
672.75 |
| Time to Peak HRRPUA (s) |
411.75 |
3580.75 |
73.25 |
| Peak HRRPUA (kW/m²) |
75.60 |
69.71 |
86.88 |
Cone Calorimeter: 50 kW/m2
|
50 kW/m² R2 |
50 kW/m² R3 |
50 kW/m² R1 |
| Time to Sustained Ignition (s) |
22.50 |
21.50 |
33.00 |
| Time to Peak HRRPUA (s) |
19.75 |
17.00 |
5.25 |
| Peak HRRPUA (kW/m²) |
180.80 |
200.27 |
200.47 |
Cone Calorimeter: 75 kW/m2
|
75 kW/m² R1 |
75 kW/m² R2 |
75 kW/m² R3 |
| Time to Sustained Ignition (s) |
12.00 |
11.50 |
11.75 |
| Time to Peak HRRPUA (s) |
27.50 |
18.50 |
14.00 |
| Peak HRRPUA (kW/m²) |
215.44 |
246.33 |
249.44 |