Measured Data
Mass Loss Rate (MLR)
Mass loss rate [g/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Tests were conducted with an edge frame set to compress the sample to a height of 40 mm.
Cone Calorimeter: 25 kW/m2
Cone Calorimeter: 50 kW/m2
Cone Calorimeter: 75 kW/m2
Heat Release Rate Per Unit Area (HRRPUA)
Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Tests were conducted with an edge frame set to compress the sample to a height of 40 mm.
Cone Calorimeter: 25 kW/m2
| 25 kW/m² R1 | 25 kW/m² R2 | 25 kW/m² R3 | |
|---|---|---|---|
| Time to Sustained Ignition (s) | 8.50 | 7.25 | 7.25 |
| Time to Peak HRRPUA (s) | 4.00 | 4.00 | 5.50 |
| Peak HRRPUA (kW/m²) | 152.20 | 114.01 | 138.28 |
Cone Calorimeter: 50 kW/m2
| 50 kW/m² R1 | 50 kW/m² R2 | 50 kW/m² R3 | |
|---|---|---|---|
| Time to Sustained Ignition (s) | 2.75 | 2.00 | 1.75 |
| Time to Peak HRRPUA (s) | 4.00 | 3.75 | 4.50 |
| Peak HRRPUA (kW/m²) | 193.23 | 136.98 | 146.98 |
Cone Calorimeter: 75 kW/m2
| 75 kW/m² R1 | 75 kW/m² R2 | 75 kW/m² R3 | |
|---|---|---|---|
| Time to Sustained Ignition (s) | 1.25 | 1.50 | 1.50 |
| Time to Peak HRRPUA (s) | 3.75 | 3.75 | 3.25 |
| Peak HRRPUA (kW/m²) | 138.61 | 144.50 | 205.76 |
Carbon Monoxide (CO) Yield
Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Tests were conducted with an edge frame set to compress the sample to a height of 40 mm.
| Incident Heat Flux [kW/m²] | Mean CO Yield [g/g] | CO Yield Std. Dev. [g/g] |
|---|---|---|
| 25 | 0.019 | 0.011 |
| 50 | 0.01 | 0.013 |
| 75 | 0.033 | 0.031 |
Derived Data
Soot Yield
Soot yield [g/g] was calculated from smoke obscuration data collected in cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Tests were conducted with an edge frame set to compress the sample to a height of 40 mm.
| Incident Heat Flux [kW/m²] | Mean Soot Yield [g/g] | Soot Yield Std. Dev. [g/g] |
|---|---|---|
| 25 | 0.013 | 0.007 |
| 50 | 0.016 | 0.018 |
| 75 | 0.014 | 0.008 |