Measured Data

Specific Heat

Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.

Unconditioned

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1767.0 39.0
20.0 1820.0 35.0
30.0 1849.0 46.0
40.0 1872.0 38.0

Dried

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1637.0 NaN
20.0 1686.0 NaN
30.0 1723.0 NaN
40.0 1733.0 NaN

Thermal Conductivity

Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.

Unconditioned

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.039 0.0
45.0 0.042 0.0

Dried

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.038 0.0
45.0 0.042 0.0

Mass Loss Rate (MLR)

Mass loss rate [kg/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.02 0.0
50 0.02 0.001
75 0.021 0.002

Specific Heat Release Rate

Experiments for specific heat release rate [W/g], were conducted using a micro-scale combustion calorimeter at a heating rate of 30 K/min.

Derived Data

Soot Yield

Soot yield [g/g] was calculated from smoke obscuration data collected in cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean Soot Yield [g/g] Soot Yield Std. Dev. [g/g]
25 0.023 0.001
50 0.028 0.007
75 0.021 0.001

Effective Heat of Combustion (Δhc)

Effective heat of combustion [MJ/kg] is calculated from data collected in both micro-scale combustion calorimeter experiments and cone calorimeter experiments.

Micro-scale Combustion Calorimeter

Value R1 R2 R3 Mean Std. Dev.
Heat of Combustion (MJ/kg) 25.5 25.26 25.35 25.37 0.1

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
25 29.7 0.4
50 30.8 0.5
75 30.7 0.3

Band Averaged Emissivity

Band averaged emissivity was calculated from reflectance measurements conducted with an integrating sphere and Fourier transform infrared spectrometer.

Source Temperature [K] Emissivity Std. Dev.
600.0 0.952 0.001
800.0 0.924 0.002
1000.0 0.887 0.004
1200.0 0.846 0.007
1400.0 0.807 0.010
1600.0 0.772 0.013
1800.0 0.742 0.016
2000.0 0.718 0.018