Measured Data

Mass Loss Rate (MLR)

Initial-mass-normalized mass loss rate [1/s] was measured in the simultaneous thermal analyzer experiments at three heating rates: 3 K/min, 10 K/min, and 30 K/min.

Simultaneous Thermal Analyzer

Derived Data

Melting Temperature and Enthalpy of Melting

Melting temperature [Tmelt] and the enthalpy of melting [kJ/kg] were derived quantities computed from data collected in simultaneous thermal analyzer experiments.

Value Mean Std. Dev.
Peak Melting Temperature (C) 263.5 3.0
Temperature at Onset of Melting (C) 246.9 1.8
Enthalpy of Melting (J/g-K) -21.4 4.6

Temperature at Onset of Decomposition

The temperature at onset of decomposition [Tonset] is a derived quantity computed from data collected in simultaneous thermal analyzer experiments.

10 °C/min 30 °C/min
Mean Onset Temperature (°C) 238 264
Std. Dev. Onset Temperature (°C) 4 4
Mean Normalized MLR at Onset (1/s) 6.96e-04 8.52e-04
Std. Dev. Normalized MLR at Onset (1/s) 1.34e-04 2.39e-04
Mean Mass Fraction at Onset 0.98 0.98
Std. Dev. Mass Fraction at Onset 0.00 0.00
Mean Temperature at end of Decomposition (°C) 392 413
Std. Dev. Temperature at end of Decomposition (°C) 57 53