Measured Data
Specific Heat
Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.
Unconditioned
Temperature (C) | Specific Heat Mean (J/kg-K) | Standard Deviation (J/kg-K) |
---|---|---|
10.0 | 1367.0 | 16.0 |
20.0 | 1425.0 | 14.0 |
30.0 | 1511.0 | 7.0 |
40.0 | 1565.0 | 15.0 |
Thermal Conductivity
Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.
Unconditioned
Temperature (C) | Conductivity Mean (W/m-K) | Standard Deviation (W/m-K) |
---|---|---|
15.0 | 0.218 | 0.003 |
45.0 | 0.233 | 0.001 |
Mass Loss Rate (MLR)
Initial-mass-normalized mass loss rate [1/s] was measured in the simultaneous thermal analyzer experiments at three heating rates: 3 K/min, 10 K/min, and 30 K/min and mass loss rate [g/s] in the cone calorimeter at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.