Measured Data
Specific Heat
Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.
Unconditioned
Temperature (C) | Specific Heat Mean (J/kg-K) | Standard Deviation (J/kg-K) |
---|---|---|
10.0 | 1623.0 | 117.0 |
20.0 | 1694.0 | 105.0 |
30.0 | 1809.0 | 120.0 |
40.0 | 1860.0 | 119.0 |
Dried
Temperature (C) | Specific Heat Mean (J/kg-K) | Standard Deviation (J/kg-K) |
---|---|---|
10.0 | 1307.0 | 105.0 |
20.0 | 1354.0 | 103.0 |
30.0 | 1403.0 | 109.0 |
40.0 | 1467.0 | 109.0 |
Thermal Conductivity
Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.
Unconditioned
Temperature (C) | Conductivity Mean (W/m-K) | Standard Deviation (W/m-K) |
---|---|---|
15.0 | 0.084 | 0.002 |
45.0 | 0.089 | 0.002 |
Dried
Temperature (C) | Conductivity Mean (W/m-K) | Standard Deviation (W/m-K) |
---|---|---|
15.0 | 0.075 | 0.002 |
45.0 | 0.080 | 0.002 |
Mass Loss Rate (MLR)
Mass loss rate [kg/s] was measured in the simultaneous thermal analyzer experiments at three heating rates: 3 K/min, 10 K/min, and 30 K/min.
Simultaneous Thermal Analyzer
Derived Data
Band Averaged Emissivity
Band averaged emissivity was calculated from reflectance measurements conducted with an integrating sphere and Fourier transform infrared spectrometer.
Source Temperature [K] | Emissivity | Std. Dev. |
---|---|---|
600.0 | 0.794 | 0.004 |
800.0 | 0.755 | 0.005 |
1000.0 | 0.710 | 0.008 |
1200.0 | 0.664 | 0.011 |
1400.0 | 0.621 | 0.014 |
1600.0 | 0.584 | 0.018 |
1800.0 | 0.554 | 0.021 |
2000.0 | 0.529 | 0.024 |